User’s Manual Fire Alarm Back-up UPS1481 UNIT Emergency Power Systems Doc #. 6002-1646 Revision X8 Installation and Operating Documentation
OnLine Power (6002-1646) REV.X8 4
OnLine Power (6002-1646) REV.X8 5 1-3 FUNCTIONAL BLOCK DIAGRAM (CONTINUED) INPUTC.B.K1132INPUT POWERT.B.TB1THE FUNTIONAL BLOCK D
OnLine Power (6002-1646) REV.X8 6 1-4 CUSTOMERS CONNECTIONS 1-4-1 Input Power Connection by Customer (with no input C/B option) Connect input
OnLine Power (6002-1646) REV.X8 7 1-4-2 OUTPUT POWER CONNECTION BY CUSTOMER FOR SAME INPUT AND OUTPUT VOLTAGE UNIT @ WITHOUT OUTPUT XFMR.
OnLine Power (6002-1646) REV.X8 8 1-4-3 OUTPUT POWER CONNECTION BY CUSTOMER FOR DIFFERENT INPUT / OUTPUT VOLTAGES USING OUTPUT XFMR.
OnLine Power (6002-1646) REV.X8 9 1-5 The Fire Alarm Back-up UPS1481 SIZING Each model of the Fire Alarm Back-up UPS1481 is designed to suppl
OnLine Power (6002-1646) REV.X8 10 The total load to be powered by the Fire Alarm Back-up UPS1481 must not exceed its rating. If the total load
OnLine Power (6002-1646) REV.X8 11 SECTION 2 - INSTALLATION 2-1 SITE PLANNING AND PREPARATION The Fire Alarm Back-up UPS1481 is designed fo
OnLine Power (6002-1646) REV.X8 12 TABLE 2-1 SITE PLANNING SPECIFICATIONS FOR KVA UNIT MODEL NUMBER IkW / kVA INPUT VOLTAGE INPUT AMP OUTPUT V
OnLine Power (6002-1646) REV.X8 13 UL1481 MICRO-CHIPS & OTHER COMPONENT’S LIST MODEL NUMBER INPUTKW / KVA OUTPUT VOLTAGE MICRO-CHIP SOFTWAR
OnLine Power (6002-1646) REV.X8 a FIRE ALARM BACK-UP UPS1481 UNIT, Congratulations on selecting one of the fine products from On-Line Power, th
OnLine Power (6002-1646) REV.X8 14 2-2 Pre-Installation The Fire Alarm Back-up UPS1481 is designed for indoor installations. All customer connec
OnLine Power (6002-1646) REV.X8 15 1. Verify that the main input circuit breaker, battery circuit breaker, and output circuit breaker(s), if prov
OnLine Power (6002-1646) REV.X8 16 3. Determine which signals will be used. Connect wires (customer-supplied) to the connector. 4. This conclud
OnLine Power (6002-1646) REV.X8 17 During long-term storage, the batteries are subject to aging and deterioration. If after visual inspection, the
OnLine Power (6002-1646) REV.X8 18 SECTION 3 - OPERATION 3-1 Start-Up Procedures 1. Verify that the main input circuit breaker, battery breake
OnLine Power (6002-1646) REV.X8 19 6. At this point in time, the Fire Alarm Back-up UPS1481 should be providing AC line power. The Fire Alarm B
OnLine Power (6002-1646) REV.X8 20 3-2-2 Turning off the Fire Alarm Back-up UPS1481 : 1. Turn off the Output Breaker(s), if provided. 2. Tur
OnLine Power (6002-1646) REV.X8 21 9. Optional Output Isolation Transformer (TI) — The transformer performs a number of critical functions. Fir
OnLine Power (6002-1646) REV.X8 22 3-4 COMPONENT’S LOCATION & LIST
OnLine Power (6002-1646) REV.X8 23 COMPONENT’S TABLE
OnLine Power (6002-1646) REV.X8 b On-Line Power, Inc. Proprietary Reproduction or Distribution forbidden NOTICE: THIS DOCUMENT CONTAINS PROPRIE
OnLine Power (6002-1646) REV.X8 24
OnLine Power (6002-1646) REV.X8 25 3-4 ITEM 18 (CONTINUED)
OnLine Power (6002-1646) REV.X8 26 APPENDIX A: EXTENDED BATTERY RUN CHART Battery kitPart# 7050-354 7050-355 7050-356 7050-357 7050-358 7050-359
OnLine Power (6002-1646) REV.X8 27 OTHERS ARE CALCULATED VALUES BASED ON THE BATTERY MANUFACTURER'S DATA FOR BACK UP TIME. APPENDIX B –
OnLine Power (6002-1646) REV.X8 28 INPUT CIRCUIT BREAKER TABLE B-3: Input Breaker Ampacity (Standard KAIC) Input Voltages KVA 120 Vac 240 V
OnLine Power (6002-1646) REV.X8 29 OnLine Power UPS Project UPS NORMAL @ 7 KW INPUT OK @ CHRG ON BATTERY OK @ DC OK ON INVERTER
OnLine Power (6002-1646) REV.X8 30 OUTPUT: ______V @ ______ W INPUT : ______V @ ______ A DC BUSS: ______V @ NA A BATT: _
OnLine Power (6002-1646) REV.X8 31
OnLine Power (6002-1646) REV.X8 32 APPENDIX D: SPECIFICATION POWER RATING (KW) 3.0 5.0 7.5 10 12.5 15 VOLTAGE (VAC) INPUT Single
OnLine Power (6002-1646) REV.X8 33 POWER RATING (KVA/KW) 3.0 5.0 7.5 10 12.5 15 BATTERY BATTERY RUN TIME See Appendix C for various Run ti
OnLine Power (6002-1646) REV.X8 c DANGER!! THIS DANGER SYMBOL IDENTIFIES A CONDITION OR ACTION WHICH WILL RESULT IN SEVERE INJURY OR DEATH TO AN
OnLine Power (6002-1646) REV.X8 34
OnLine Power (6002-1646) REV.X8 35
OnLine Power (6002-1646) REV.X8 36 + + + + + + + + + + 2ND LEVEL
OnLine Power (6002-1646) REV.X8 37 + + + + + + + + + + #6 #7 #5 #4 #
OnLine Power (6002-1646) REV.X8 38 + + + + #8 #7 #6 #5 + + + + #4 #3 #2 #
OnLine Power (6002-1646) REV.X8 39
OnLine Power (6002-1646) REV.X8 40
OnLine Power (6002-1646) REV.X8 41
OnLine Power (6002-1646) REV.X8 42
OnLine Power (6002-1646) REV.X8 43
OnLine Power (6002-1646) Rev. X8 i TABLE OF CONTENTS SECTION PAGE SECTION 1 OPERATION 1 1-1 INTRODUCTION 1 1-2 BENEFITS
OnLine Power (6002-1646) REV.X8 44
OnLine Power (6002-1646) REV.X8 ii REVISION HISTORY REV DATE PRIMARY REASON FOR CHANGE X1 APRIL 4, 2004 RELEASE FOR PRODUCTION X2 FEB 2
OnLine Power (6002-1646) Rev. X8 1 SECTION 1 — OPERATION 1-1 INTRODUCTION The Fire Alarm Back-up UPS1481 provides an exceptional level of load
OnLine Power (6002-1646) REV.X8 2 systems, from electrical interference. The Fire Alarm Back-up UPS1481 protects these systems from power problems
OnLine Power (6002-1646) REV.X8 3 Optional Output Isolation Transformer — This transformer is provided when the input and output voltages are diff